The following items are required to properly installthe OMEGA FP-6000 Series Adjustable Brass flowsensor.3.1 Hardware, Standard Sensor• female pipe fi

Page 3 - Contents

54. Remove brass sensor nut from sensor.5. Thread brass sensor nut into pipe fitting.3.4 Hot-Tap Fitting Installation1. Install the pipe fitting on t

Page 4

64. Open the isolation valve and insert the drillthrough the valve and cut the sensor clearancehole. After the hole is cut, withdraw the drill fromth

Page 5 - Important Safety Information!

7Standard SensorH = 5.95 - pipe wall thickness - (0.10 X I.D.)Example:3.0 inch schedule 80 wrought steel;Wall thickness= 0.3 in.Inside diameter = 2.9

Page 6 - 10 inch brass alignment rod

8Once the correct dimensions are calculated andrecorded, the sensor can be installed in the fitting.The Standard and Hot-Tap versions requiresubstanti

Page 7 - Introduction

94. Place the alignment rod in the hole on thesensor flange. Align the flange so rod is parallelto the process pipe.5. Thread upper hex nuts with loc

Page 8 - Installation and

103.7 Hot-Tap Installation1. Thread one hex nut onto each of the threethreaded rods included in package. Installthreaded rod with a lock-washer onto

Page 9 - 2.3 Sensor Wiring

alignment rodsensor flangeprocess pipe (top view)The flow sensor alignment rod MUST be parallel to the process pipe as shown.direction of flowsensor f

Page 10 - Installation

12Using the Hot-Tap Installation ToolThe Hot-Tap installation tool helps to lower thesensor into place against the pressure in the pipe.1. Thread prot

Page 11 - (Teflon tape recommended)

133. Align the sensor cable with the swivel mountcable port to prevent cable pinching. Use a3/8 inch wrench or socket to turn the installationtool sh

Page 12

It is the policy of OMEGA to comply with all worldwide safety and EMC/EMI regulations thatapply. OMEGA is constantly pursuing certification of its pro

Page 13 - "H"

144.1 Standard Sensor RemovalTo remove the Standard FP-6000 Series sensorfrom a depressurized empty pipe, simply removethe cap nuts and upper hex nuts

Page 14 - 3.6 Standard Installation

155. Wearing safety face protection, turn theinstallation tool shaft counterclockwise to withdrawsensor until the sensor flange contacts the upperhex

Page 15 - (151 mm)

5.1 MaintenanceAll versions of the FP-6000 series sensor requirelittle or no maintenance, with the exception of anoccasional sensor/paddlewheel cleani

Page 16 - 3.7 Hot-Tap Installation

175.3 Rotor Replacement Procedure1. With a small pair of needle-nose pliers, firmlygrip the center of the rotor pin (axle) and with atwisting motion,

Page 17 - 1/4 in. lock washers

5.644 in.5.589 in.5.500 in.5.427 in.5.369 in.5.310 in.5.187 in.5.064 in.4.830 in.4.583 in.4.350 in.4.200 in.3.950 in.3.700 in.3.475 in.*3.000 in.18NPS

Page 18 - Protector plate

1914.694 in.14.639 in.14.550 in.14.477 in.14.419 in.14.360 in.14.237 in.14.144 in.13.880 in.13.633 in.13.400 in.13.250 in.13.000 in.12.750 in.12.525 i

Page 19

K-factorsStainless SteelSCH 5S STAINLESS STEEL PIPE PER ANSI B36.19K-FACTOR K-FACTOR A-FACTOR A-FACTORPIPE PULSES/ PULSES/ U.S.SIZE U.S. GAL LITER GPM

Page 20 - Procedures

K-factorsWrought Steel21STD WROUGHT STEEL PIPE PER ANSI B36.10K-FACTOR K-FACTOR A-FACTOR A-FACTORPIPE PULSES/ PULSES/ U.S.SIZE U.S. GAL LITER GPM/HZ L

Page 21

22K-factorsPlastic PipeTo convert K from to multiply K byU.S. gallons cubic feet 7.479U.S. gallons cubic inches 0.00433U.S. gallons cubic meters 263.8

Page 22 - Refer to rotor replacement

23SpecificationsGeneral DataFlow velocity range: 1.6 to 20 ft/s0.5 to 6 m/sLinearity: ±1% of full rangeRepeatability: ±0.5% of full rangePipe sizes:St

Page 23 - Retainer

Table ofContentsChapter Page1 Introduction 11.1 Description 11.2 Theory of Operation 12 Installation and Wiring 22.1 Location of Fitting 22.2 Sensor P

Page 24 - H Dimensions

operating pressure: 225 psi (15 bar)Maximumoperating temperature: 212°F (100 °C)Caution: The FP-6002 and FP-6003 Series Hot-Tap system's overall

Page 25

WARRANTY/DISCLAIMEROMEGA ENGINEERING, INC. warrants this unit to be free of defects in materials and workmanship for aperiod of 13 months from date of

Page 26 - Stainless Steel

6-2517.090-OM/(D-8/02) M-2973/0802Where Do I Find Everything I Need forProcess Measurement and Control?OMEGA…Of Course!Shop online at www.omega.comTEM

Page 28 - Plastic Pipe

Important Safety Information!CAUTION:(Standard version) Never remove the flow sensorfrom a pressurized pipe. Always wear safety faceprotection during

Page 29 - Specifications

Unpacking and InspectionYour flow sensor package includes the followingitems:OMEGA FP-6000 Series Adjustable Brass Flow Sensor6 inch ruler (Standard s

Page 30

Chapter 1IntroductionThis manual contains description, specificationsand instruction for the installation, removal, andoperation of the OMEGA FP-6000

Page 31 - RETURN REQUESTS/INQUIRIES

The linearity and accuracy of the FP-6000 Seriessensor depend on predictable flow conditions inthe pipe and proper location of the fitting. Aswith a

Page 32 - Shop online at www.omega.com

3(max. 30°) will help to avoid these problem areas,but use caution. Excessive angles will causebearing drag at lower flow rates.On a vertical pipe ru